Advanced Analysis of Dew Point Control Unit of Hybrid Refrigeration Systems in Gas Refineries
Message:
Article Type:
Research/Original Article (دارای رتبه معتبر)
Abstract:
In this paper, an advanced analysis of a novel hybrid compression-absorption refrigeration system (HCARS) for natural gas dew point control unit in a gas refinery is presented. This unit separates the heavy hydrocarbon molecules in the natural gas, which is traditionally carried out by natural gas cooling in a compression refrigeration cycle (CRS). The power input required for the refrigeration cycle compressors is usually provided by gas turbines. The low efficiency of gas turbines and the excessive power required for running the CRS compressors have made it crucial to investigate different means to decrease the energy consumption of this cooling system.
The waste heat of gas turbines flue gas can be recovered and utilized as the heating source for running an absorption refrigeration system (ARS) to provide part of the needed cooling load; hence, a hybrid compression absorption refrigeration system (HCARS) is launched. In this work, the application of HCARS is extended to the Fajr-e-Jam gas refinery currently operating with a CRS, and an advanced exergetic analysis of the proposed ARS is performed to further improve the proposed system. The effect of different variables on the performance of the proposed HCARS is also inspected. The proposed system and these analyses are novel for the gas refinery dew point control unit. Real CRS operational data are utilized in all the investigations, and proper means are presented for the validation of the simulation results.
The proposed system resulted in 63% additional cooling capacity of the HCARS (12550 KW) in comparison to the current CRS (7670 kW) for the equal natural gas consumption, which overall saves about 50000 SCMD of natural gas. Based on the exergy analysis of all the equipment, the exergy efficiency of the proposed ARS is 0.155. In addition, the parametric study of the effects of the gas turbine flue gas exit temperature and flow rate, ambient temperature, partial load operation of CRS, absorption solution flow rate, and concentration on the HCARS performance is carried out. These studies should provide the information needed for operating the proposed system in different situations
Language:
English
Published:
Iranian Journal of Oil & Gas Science and Technology, Volume:7 Issue: 3, Summer 2018
Pages:
32 to 52
magiran.com/p1897165  
دانلود و مطالعه متن این مقاله با یکی از روشهای زیر امکان پذیر است:
اشتراک شخصی
با عضویت و پرداخت آنلاین حق اشتراک یک‌ساله به مبلغ 990,000ريال می‌توانید 70 عنوان مطلب دانلود کنید!
اشتراک سازمانی
به کتابخانه دانشگاه یا محل کار خود پیشنهاد کنید تا اشتراک سازمانی این پایگاه را برای دسترسی نامحدود همه کاربران به متن مطالب تهیه نمایند!
توجه!
  • حق عضویت دریافتی صرف حمایت از نشریات عضو و نگهداری، تکمیل و توسعه مگیران می‌شود.
  • پرداخت حق اشتراک و دانلود مقالات اجازه بازنشر آن در سایر رسانه‌های چاپی و دیجیتال را به کاربر نمی‌دهد.
دسترسی سراسری کاربران دانشگاه پیام نور!
اعضای هیئت علمی و دانشجویان دانشگاه پیام نور در سراسر کشور، در صورت ثبت نام با ایمیل دانشگاهی، تا پایان فروردین ماه 1403 به مقالات سایت دسترسی خواهند داشت!
In order to view content subscription is required

Personal subscription
Subscribe magiran.com for 50 € euros via PayPal and download 70 articles during a year.
Organization subscription
Please contact us to subscribe your university or library for unlimited access!