Mitigation Transformer Inrush Current Using Modified Transient Current Limiter
Author(s):
Article Type:
Research/Original Article (دارای رتبه معتبر)
Abstract:
This study presents a modified transient current limiter (MTCL) for mitigation the inrush current of transformers. The MTCL is based on conventional transient current limiter (TCL), which, its configuration is modified to overcome the TCL drawbacks of operation. The proposed MTCL offers lower power losses and voltage/current THD during normal operation mode. It needs only one limiting reactor instead of two limiting reactors, which results in cost saving. The theoretical analysis of the MTCL for suppressing the inrush current has been presented and the performance was tested by PSCAD/EMTDC simulation anda experimental prototype. Both simulation and experimental results showed that the MTCL is effective for suppressing the transformer inrush current. Also, the capability of the MTCL for suppressing the transformer inrush current was compared with the conventional TCL.
Keywords:
Language:
English
Published:
International Journal of Engineering, Volume:32 Issue: 5, May 2019
Pages:
701 to 709
https://www.magiran.com/p1979483
سامانه نویسندگان
مقالات دیگری از این نویسنده (گان)
-
Hybrid k-means-PSO Technique for Transformer Insulation Moisture Determination in the Production Stage Based on Frequency Response Analysis
M. Bigdeli*
Iranian Journal of Electrical and Electronic Engineering, Mar 2022 -
Estimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
*, Jafar Aghajanloo, Davood Azizian
Journal of Modeling and Simulation in Electrical and Electronics Engineering, Winter 2021