Wavelet Transform based Detection and Classification of Multilocation Three Phase to Ground Faults in Twelve Phase Transmission Line
In this study, wavelet transform is applied for three phase to ground fault detection and classification which occur at different locations in a 765 kV, 50 Hz twelve phase transmission line. The information of distorted energy, approximate and high frequency detail coefficients included in a fault current signal is captured using wavelet transform. Faulted phase determination is also carried out using the proposed technique concurrently. The effectiveness of the proposed protection technique is validated for three phase to ground faults, and various values of fault type, fault inception time, fault resistance, and fault location. Test results show that the proposed technique effectively detects the three phase to ground fault and discriminates the faulty phase effectively.
- حق عضویت دریافتی صرف حمایت از نشریات عضو و نگهداری، تکمیل و توسعه مگیران میشود.
- پرداخت حق اشتراک و دانلود مقالات اجازه بازنشر آن در سایر رسانههای چاپی و دیجیتال را به کاربر نمیدهد.