Structural Behavior of Reinforced Concrete Horizontally Curved Box Beam with Opening
This work is dedicated to survey the structural reinforced concrete's behavior horizontally curved box beams with and without opening. Seven horizontally circular box beams were examined in the experimental work, one without opening, three with vertical opening and three with transverse opening. The test program includes the main variables; direction of opening, location of opening through profile of curved beams (effect of combination of internal forces). The beams were tested as a continuous beam with two spans, each span represents a quarter circle and under the action of two point loads each load located at top face of midspan of beam. The findings indicate that the ultimate load capacity was decreased for all specimens (CB2.V37, CB3.V60, CB4.V82, CB5.T37, CB6.T60 and CB7.T82) by about (5%, 11.5%, 1.5%,1.5%, 46.4% and 18.66%) respectively, compared to the control CB1. When compared with the control specimen CB1, all specimens were indicating an increase in Service deformations in terms of deflection and twisting angle at mid-span of the circular beams. The ductility was deteriorated for all specimens with opening (CB2.V37, CB3.V60, CB4.V82, CB5.T37, CB6.T60 and CB7.T82), as a percent were about (13.88%, 15.3%, 19.62%, 0.5%, 0.5% and 13.88%) respectively, compared with that of control specimen CB1. Generally, the specimens containing opening were shown a clear degradation in its stiffness.