Corrosion and scaling in Bandar Abbas Pipe water network
Scaling and corrosion is one the most important indices in water quality evaluation. Occurrence of scaling or corrosion may create disorder in economy of water and wastewater industry. In addition corrosion produces by - products in water leading to health problem and reduction of water pipe life-time. In this study, the condition of scaling and corrosion in Bandar Abbas water network was been evaluated.
In this cross- sectional study, pipe water network of Bandar Abbas was divided into 15 sections and, randomly 3 samples were taken from each section. Langleier and Rysnar indices and Marble test were used for water quality analysis.
Based on Rysnar index, in 20% of samples, water was neutral and in 33% as slightly corrosive. Based on Langleier index in 6.6% of samples, water was neutral and in 93.4% were slightly corrosive. Marbel test showed that all of the tested samples were corrosive.
We showed that, there is corrosion potential in Bandar Abbas water network so as proper interference is required. By evaluation of indices, there is significant difference among indices findings; therefore it seems that of mono-index evaluation is likely unable to determine the corrosion status or scaling condition. To evaluate water stability or corrosiveness condition, Langleier and Rysnar indices and along with Marble test is recommended to be applied at a time.
- حق عضویت دریافتی صرف حمایت از نشریات عضو و نگهداری، تکمیل و توسعه مگیران میشود.
- پرداخت حق اشتراک و دانلود مقالات اجازه بازنشر آن در سایر رسانههای چاپی و دیجیتال را به کاربر نمیدهد.